Single-phase pole-mounted distribution transformers are designed for servicing residential overhead distribution loads. They are also suitable for light commercial loads, industrial lighting and diversified power applications.
Aanvraag sturen
Praat nu

Heeft u vragen? GNEE-vertegenwoordigers zijn nu beschikbaar voor livechat

E-mail- verzenden:sales@gneeelectric.com

Telefoon:+8615824687445

 

are designed and manufactured in compliance with all applicable IEEE and RUS standards. All transformers are oil filled, 65 degree rise, and designed for usual service conditions per IEEE C57.12.00.Polemount transformers are categorized by type and class. Type identifies the protection of transformers. Class Identifies the number of high voltage bushings, mounting positions and lightning arresters when required.

H.V. L.V. E
A B C D
10 34500/19920
or33000/19100
±2×2.5% or
0
120 240 277 480 or
120-240 240-480
36 120 850 500 567 380 286 591 610 100
15 50 195 1100 505 570 380 135
25 80 290 1220 545 620 420 200
37.5 105 360 1250 585 660 460 250
50 135 500 1285 635 710 510 310
75 190 650 1320 660 730 510 360
100 210 850 1355 720 730 560 410
167 350 1410 1456 800 848 560 570
250 500 2000 1518 880 908 620 815
333 650 2500 1550 1020 1018 680 870

Pole distribution transformer

:

External welds are 100% coverage for added strength and corrosion withstand.

100% of the polemount receives a paint finish that exceeds all IEEE requirements including 160 in-lb. impact, 2000-hour salt spray, 1000 hours QUV and 20 cycle SCAB.